Page 8 - Data, Network and Bus Technology
P. 8
i!I), HI·TECH (800) 877·8842 I (303) 880·5159 www.hltechcontrols.com
~ CONTROLS, INC. Click or Call for a Quotel
BUS Cables I: HELUKA""L"
CAN BUS, NFPA 79 Edition 2007
-
Type Flexible indoor
Cable Structure 2x2xO.34 qmm (stranded)
Inner conductor diameter: Bare copper (AWG 19)
Core insulation: PP
Core colours: wh/br, ye/gn
Stranding elements: Double-core
Screen 1: Polyester foil over stranded bundle
Screen 2: Polyester foil, AI-coated
Overall screening: Cu braid tinned
Outer sheath material: PVC
Cable outer diameter: Approx. B.5 +·0.3 mm
Outer sheath colour: Violet, similar to RAl4001
Electrical Data
Impedance: 120 Ohm +. 10%
Conductor resistance: < ~ 55.4 Ohm/km
Insulation resistance: 5.00 GOhm x km min.
Operating capacity: 42.0 nF/km nom.
Test voltage: 1.5 kV
Technical Data
Weight: approx. 85.0 kg/km
Min. bending radius during installation: 225.0 mm
Operating temperature range min.: ·40' C
Operating temperature range max.: + 80' C
Copper weight: 46.0 kglkm
Standards
Applicable standards: Profibus in ace. with DIN 19245 T3 and EN 50170
UL style: c(UL)us CMX in accordance with UL 444
Application
The CAN bus series (Control Area Network) is a variable field bus system. Used to network complex controllers and control
units in automation technology applications. The textile and construction machine industry and medical technology sedor use
this model series. Certified to UL, the cable can also be used in the USA and Canada.
Part No: 803344, CAN Bus
IC HELUKABEL