Page 9 - Data, Network and Bus Technology
P. 9
i!I), HI·TECH (800) 877·8842 I (303) 880·5159 www.hltechcontrols.com
~ CONTROLS, INC. Click or Call for a Quotel
BUS Cables I: HEWKABEa:
HELUWINO" WK CAN BUS 10S·C
-
Type Flexible indoor
Cable 5tructure 2x2xO.25 qmm (stranded)
Inner conductor diameter: Bare copper (AWG 24/19)
Core insulation: XPE
Core colours: wh/br. ye/gn
Stranding elements: Double-core
Screen 1: Polyester foil over stranded bundle
Screen 2: Polyester foil, AI-coated
Overall screening: Cu braid tinned
Outer sheath material: PUR
Cable outer diameter: Approx. 8.4 +·0.3mm
Outer sheath colour: Violet, similar to RAl4001
Electrical Data
Impedance: 120 Ohm +. 10%
Conductor resistance: <= 87.2 Ohm/km
Insulation resistance: 1.00 GOhm x km min.
Operating capacity: 42.0 nF/km nom.
Test voltage: 1.5 kV
Technical Data
Weight: approx. 80.0 kg/km
Min. bending radius during installation: 126.0 mm
Operating temperature range min.: -40' C
Operating temperature range max.: + 1 OS·C·
Copper weight: 40.0 kglkm
5tandards
Applicable standards: Profibus in ace. with DIN 19245 T3 and EN 50170
UL style: UIJCSA 80' C, 600 V
Application
The CAN bus series (Control Area Network) is a variable field bus system. Used to network complex controllers and control
units in automation technology applications. This cable with its oil-resistant PUR sheath and increased temperature resistance
is employed in the wind turbine and similar sectors. Certified to UUCSA, the cable can also be used in the USA and Canada.
Part No: 801982, CAN Bus WK 10S·C
.,. = With limited service life
IC HELUKABEL