Page 7 - Data, Network and Bus Technology
P. 7

i!I), HI·TECH                               (800) 877-8842 I  (303) 880-5159           www_hltechcontrols_com
  ~ CONTROLS, INC.                               Click or Call for a  Quotel

   BUS Cables                                                                                  I:  HEWKARE':

                                                                                                                CAN BUS


                                                   -














   Type                                      Flexible indoor                           Flexible indoor
   Cable Structure                           1x2xO_75 qmm                              4x1xO_75 qmm
                                             (stranded)                                (stranded)
   Inner conductor diameter:                 Tinned copper (AWG  19)                   Tinned copper (AWG  19)
   Core insulation:                          Foam Skin  PE                             Foam Skin  PE
   Core colours:                             wh,  br                                   wh, br,  gn, ye
   Stranding elements:                       Double-core                               Star quad
   Screen  1:                                Polyester foil over stranded bundle       Polyester foil over stranded bundle
   Screen 2:
   Overall screening:                        Cu  braid tinned                          Cu  braid  tinned
   Outer sheath  material:                   PVC                                       PVC
   Cable outer diameter:                     Approx. 8.4  +-0.4 mm                     approx.  9.1  +-0.4 mm
   Outer sheath colour:                      Violet, similar to RAL 4001               Violet, similar to RAL 4001

   Electrical Data
   Impedance:                                120 Ohm  + -10%                           120 Ohm  +-10%
   Conductor resistance:                     27.4 Ohm/km max.                          27.4 Ohovkm max.
   Insulation resistance:                    1 GOhm x km  min.                         1 GOhm x km min.
   Operating capacity:                       36 nF/km nom.                             36 nF/km nom.
   Test voltage:                             1.0 kV                                    1.0 kV

   Technical Data
   Weight:                                   approx. 91.0 kg/km                        approx.  105.0 kg/km
   Min. bending radius during installation:   126.0 mm                                 138.0 mm
   Operating temperature range min.:         -25°C                                     -25°C
   Operating temperature range max.:         + 70°C                                    + 70°C
   Copper weight:                            40.0 kg/km                                58.0 kg/km
   Standards
   Applicable standards:                     Profibus in ace.  with DIN  19245 T3      Profibus in ace.  with DIN  19245 T3
                                             and  EN50170                              and  EN50170
   UL style:                                 UL style 2571                             UL style 2571

   Application
   The CAN  bus series (Control Area  Network) is a variable field bus system.  Used to network complex controllers and control
   units in automation technology applications. The textile and construction machine industry and  medical technology sedor use
   this model series. The cables described here are designed for fixed installation indoors. This is a very cost-effective BUS  system.

   Part No:                                  803383, CAN  BUS                          803384, CAN  BUS






                                                       IC  HELUKABEL
   2   3   4   5   6   7   8   9   10   11   12