Special silicone multi conductor
cable with higher heat-resistance
range adapted to DIN VDE 0250
part 1 and part 816
Temperature Range -60°C
to
+180°C (-76°F
to
+356°F)
(Up to +220°C for short time)
Temperature Limit at
the Conductor In
operation
+180°C/+356°F
Nominal Voltage U0/U
300/500 V
Test Voltage 2000
V
Breakdown Voltage min.
5000 V
Insulation Resistance Min.
200
MOhm
x km
Power Rating At ambient temperature
up to 145°C/293°F
to DIN VDE 0100 for higher temperatures
valid:
150°C/302°F- load value 100%
155°C/311°F - load value 91%
160°C/320°F - load value 82%
165°C/329°F - load value 71%
170°C/338°F - load value 58%
175°C/347°F - load value 41%
Radiation Resistance Up
to
20x106 cJ/kg
(up
to
20
Mrad)
Approvals
Cable
Construction
Tinned copper conductors to DIN VDE
0295 cl. 5, BS 6360 cl. 5 and IEC 60228
cl. 5
Silicone conductor insulation
Conductor identification to DIN VDE 0293-308
color coded or black conductors with continuous
white numbers
For 2-conductors brown, blue
Conductors stranded in layers with optimal
lay-length
Green-yellow earth-conductor (3 conductors and
above)
Outer jacket of silicone
Jacket color: Preferably red brown
Application
Silicone cables
were designed for use wherever
insulation is subjected to extreme
temperature changes. They are heat
resistant for permanent temperatures
up to +180°C/+356°F, and short time
for operation to +220°C/+428°F. These
cables have great environmental
resistance properties and can be
used at temperatures as low as
-60°C/-76°F. Silicone cables are
halogen-free and are especially
suitable for installation in power
stations. They have also found
their uses in steel producing industries,
aviation industry, ship building
as well as in ceramic, glass and
cement factories.
Due to the elastic characteristic of conductor insulations, these are used as flexible connection cable. =
The product is conformed with the
EC Low-Voltage Directive 73/23/EEC
and 93/68/EEC.
Properties
Advantages: Minimal changes of dielectric
strength and the insulation resistance
also at high temperatures, high ignition
or flash point, in case of fire, forms
an insulating layer of SiO2
Resistant to high molecular
oils, fats from
vegetables and
animals, alcohols,
plasticizers and
clophenes, diluted
acids, lye and
salt dissolution,
oxidation substances,
tropical influences
and weather, lake
water, oxygen and
UV
Halogen-free according
to DIN VDE 0482
part 267 / EN 50267-2-2 /
IEC 60754-2 (equivalent
DIN VDE 0472 part
813)
Behavior in fire no flame
propagation
test according to DIN VDE 0482 part 265-2-1 /
EN 50265-2-1 / IEC 60332-1 (equivalent
DIN VDE 0472 part 804 test method B)
For laying as a fixed installation
only in open or ventilated pipe systems
as well as in ducts. Otherwise the mechanical
properties of the silicon are reduced
by the enclosed air at temperatures exceeding
90°C.
Note
G = with green-yellow grounding
x = without green-yellow grounding (OB)
is the Exclusive Importer of HUMMEL products. We offer over 6,000 different Types and Sizes of RoHS Compliant Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands, Circular Connectors, Conduit System, Industrial Enclosures and Other Related Cable Management Products which are rated the best in the industry.
Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands Threads: PG, NPT, Metric, BSPP Threads Materials: Nylon, Nickel Plated Brass, PVDF (for chemicals and extreme temperatures) & Stainless Steel,
NEMA 4x and 6 (IP68, IP 69K). Approvals: RoHS, Deca BDE, UR, UL, CE, CSA, VDE, German Lloyd, etc. UL f1 (UL 746C) - Suitable for outdoor use with respect to exposure to ultraviolet light, water exposure and immersion in accordance with UL 746C
Circular Connectors (M16, M23, RJ45, M27 and M40) Sizes: M16 Signal, M23 Signal & Power, M27 Signal, M40 Power, M12/16 Twintus Types: Twintus, RJ45 Industrial Ethernet, PoE Fast Ethernet, Push-Pull, Stainless Steel, Over Molded Cordsets, Standard/EMI Ready Configurations: Signal (3-28 pole) & Power (6 & 8 pole) Materials: Nickel Plated Brass, Stainless Steel and Aluminum Approvals: RoHS, Deca BDE, UR, UL, CSA, TÜV, etc.
Industrial Enclosures (Plastic & Metal) Materials: Polycarbonate, ABS (Acryl-Butadiene-Styrene), Aluminum, Steel/Stainless Steel and Polyester. Types: Gray or Transparent Lids, available with Hinges and Latches, Plain Walls or Knockouts. Approvals: RoHS, Deca BDE, UL, CSA, TUV and CE.
Modular, Expandable, UV and Impact Resistant, NEMA 4, 4x (IP 66/67). Solar Plus for Photovoltaic applications.
Our Enclosures can be equipped with Strain Relief Fittings, Circular Connectors or Conduit Fittings. Other customization options like cutting & drilling are also available.
Conduit System
High Pull-Out Resistance, Robust Performance, Long Life Expectancy, Fastest/ Easy installation, No Tools required!
Fittings: Push-In, Turn-to-Seal, Snapclic DUO (Nylon or Nickel Plated Brass), Double-Seal, Flange/Bulkhead
Conduit: Standard and Super Flex Corrugated Conduit Accessories: Snap-In Mounting Brackets. NEMA 4 (IP 54/65) Approvals: RoHS, Deca BDE, UR, German Lloyd, CE, etc.
Hazardous Location / Explosive Proof Cord Grips, Cable Glands
These fittings are labeled and approved to withstand the required needs of a combustible environment. Materials: Nylon, Nickel Plated Brass, PVDF (chemical resistant & extreme temperatures), Stainless Steel. Threads: NPT, Metric & PG. NEMA 4x (IP 67) and 6 (IP 68/69K)
Approvals: RoHS, Deca BDE, UL, CSA, VDE, CE, EEx e, ATEX, German Lloyd, IECEx,
Ex-d/Ex-e, Ex-i EXIOS - High-end Cable Glands for armored cables in hazardous areas including the latest IECEx and ATEX certifications, for use in Ex-e, Ex-d and Ex-tD areas
Thread Adapters, Enlargers, Reducers
Convert, Increase or Decrease your thread size with our newest product line of Adapters, Enlargers and Reducers. Threads: NPT, Metric and PG. Materials: Black or Gray Nylon, Nickel Plated Brass, Aluminum, Stainless Steel. Approvals: RoHS, Deca BDE, CE, EEe x, ATEX, etc.
Hazardous / Explosive proof versions available.