Page 4 - Power Cables
P. 4
i!I), HI·TECH (800) 877-8842 I (303) 880-5159 www_hltechcontrols_com
~ CONTROLS, INC. Click or Call for a Quotel
N 2XV power cable 0.6/1 kV, VOE approved
-
- N2XY <lVDEt> 0276 0,611 kV
I RoHS I
Technical Data Cable Structure Properties
• Power and control cable according • Bare copper conductor according to • Self-extinguishing and flame retardant
to DIN VDE 0276 Part 603 5t or DIN VDE 0295 d. 1 or d. 2, single-wire in accordance with VDE 0482-332-1-2,
HD 603. t and lEe 60502 or multi-wire, BS 6360 cl. 1 or d . 2, DIN EN 60332-1-2/ lEe 60332-1
• Temperature range lEe 6022B d . 1 or d. 2 or HD 383 (conforms to DIN VDE 0472 Part 804
Flexing -SoC to +SOO( • Core insulation from cross-linked Test method B)
Fixed installation _400( to + 70 e polyethylene compound, D1X3 • The materials used in manufacture are
0
• Permissible operating temperature according to HD 603.1 free of silicone, cadmium and sub-
0
at the conductor +90 ( • Cores stranded in concentric layers stances that impair paint wetting
• Permissible short circuit • Core colours in accordance with Highest permissible voltage
0
temperature +250 ( (short-circuit DIN VDE 0293-308, 0276 Part 603 • Direct current systems 1.8 kV
duration 5 sec.) or HD 186 • Three-phase systems
• Nominal voltage • PVC outer sheath, DMV6/DMP2 Single-phase systems:
Ud U 0.6/1 kV according to HD 603.1 Both outer conductors insulated 1.4 kV
• Test voltage 4 kV • Sheath colour - black Single-phase systems:
Max. permissible tensile load One outer conductor earthed 0.7 kV
with cable grip = 50 N/mm2 • Three-phase system 1.2 kV
• Minimum bending radius
Single-core approx. 15x cable 0 Notes
Multi-core approx. , 2x cable 0 • re = round conductor, single-wire;
rm = round conductor, multi-wire;
sm = sector-shaped conductor,
multi-wire.
Application
Power distribution cables for use underground, in water, outdoors, in concrete, indoors, in cable ducts, for power
stations, industrial applications and switching systems, as well as in local networks if no mechanical damage is
0
expected. Respecting the permissible operating temperature at the conductor of + 90 ( permits a higher current
carrying capacity than PVC insulated power distribution cables.
(€ ~ The product conforms to the EG Low-Voltage Directive 2006/95/EG.
Number Outer " Co p. Weight Weig ht Hype O·type
of cores ~ mm kglkm a ppro~. kglkm Part No. Part No.
no m;n<tl cron
5('<t;on mm'
lxl6re 11,5 ' 50 32850 32862
1x25rm 12,5 2<0 '" 32851 32863
362
lx35rm 13.5 336 "0 32852 32864
1x50rm 15,5 "0 620 32853 32865
lx70rm 17,0 80S 32854 32866
'"
lx95rm 19,0 '" " .. 32855 32867
1108
h,20rm 20,5 1152 32856 32868
h150rm 23.0 1610 32857 32869
1776
h185rm 25.5 "" 2050 32858 32870
ld40rm 28,5 2304 2635 32859 32871
lx300rm 30,0 2880 3200 32860 32872
l x400rm " .0 4150 32861 32873
" ..
4x16rm 21 ,5 "" 32814 32884
960
4x25rm 26,0 '" "" 32875 32885
4x35rm 27,5 1344 "" 32876 32886
4~50~m 30,0 1920 2350 32877 32887
4x70sm 34,0 2688 3>00 32818 32888
4x95sm 39,0 36" 4250 32879 32889
4x120sm 42.5 4608 5300 32880 32890
4xl 50sm 47,5 5760 6<00 32881 32891
4x185sm 52.0 7104 8500 32882 32892
4x240sm 58,0 9216 " 000 32883 32893
~ MId ~toorn ~ bt ct,.,-,g.ed ... tnout PI"" nob«