Current Ratings - Conversion Factors: for grouping on walls, on the floor, in insulation tubes or in conduit and under the ceiling

Number of Multi conductor cables or number of a.c. or 3-phase circuits of single conductors 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20
Installation Methods Conversion Factors
One layer under the ceiling with contact
One layer under the ceiling with contact
0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.61 0.61 0.61 0.61 0.61 0.61 0.61
One layer under the ceiling with a space equal to outer diameter (d)
One layer under the ceiling with a space equal to outer diameter (d)
0.95 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85
One layer on the wall or floor with a space equal to outer diameter (d)
One layer on the wall or floor with a space equal to outer diameter (d)
1.00 0.94 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9
One layer on the wall or floor with contact
One layer on the wall or floor with contact
1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.7 0.7 0.7 0.7 0.7 0.7 0.7
Bunched directly on the wall, on the floor, in insulating tubes or trunking or in the wall (see image below)
1.00 0.8 0.7 0.65 0.6 0.57 0.54 0.52 0.5 0.48 0.45 0.43 0.41 0.39 0.38
Bunched directly on the wall, on the floor, in insulating tubes or trunking or in the wall

Notes:
These factors are to be applied for the calculation of power ratings, the same type of cables and with equal loaded conductors in the same installation method shall correspond.
At the same time the cross-section are permitted to differ maximum one grade of cross-section.

If the actual horizontal-space between the adjacent cables is more than double of the outer diameter, no reduction factor is necessary

The same reduction factors are to be applied for grouping of two or three-conductor or multi conductor cables. For a system consisting of two or as well as three-conductor cables, firstly the total number of cables will be assumed as the number of circuits. For that the applicable factor is to be used either in the tables for two-conductor loaded cables or the tables for three- conductors loaded cables.

If the grouping of single conductor cables consist of n loaded single conductor cables, the rating factor shall be determined for n/2 or n/3 circuits and applied to the current carrying capacity of two or three loaded conductors.

quote
Items For Quote

   
quote
box
Sealcon is the Exclusive Importer of HUMMEL products. We offer over 6,000 different Types and Sizes of RoHS Compliant Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands, Circular Connectors, Conduit System, Industrial Enclosures and Other Related Cable Management Products which are rated the best in the industry.
7374 S. Eagle Street
Centennial, CO 80112-4221 USA
Toll Free: 800-456-9012 / 303-699-1135 FAX: 303-680-5344
Valid XHTML 1.0 Transitional
To Top of Page Top of Page

Copyright © Sealcon All Rights Reserved
|Domestic & International Cables|Enclosures |Liquid Tight Strain Relief Fittings & Accessories|
|Circular Connectors|Conduit System|Pneumatics|Cable Index|Enclosure Index|Search|
|Media|Site Map|Company Overview|Contact|Privacy Policy|Copyright Notice|