Operating temperature at conductor 90°C; Ambient temperature 30°C
Type Designation |
NI2XY, N2XY, N2X2Y, N2XH, N2XCH1), NHXHX FE 180, NHXCHX FE 1801), NHXH FE 180, NHXCH FE 1801), NHXHX, NHXCHX1) |
Installation:
- Direct
- Open Air |
Single - or Multi Conductor Cables on a wall
|
or |
|
|
Multi Conductor Cables with a space of min. 0.3 x diameter (d) to wall
|
Installation Method2) |
Direct Installation |
Installation in Open Air |
C |
E |
Number of Loaded Conductors |
2 |
3 |
2 |
3 |
Cross-section in mm² |
Current Ratings in Ampere (A) |
1.5 |
24 |
22 |
26 |
23 |
2.5 |
33 |
30 |
36 |
32 |
4 |
45 |
40 |
49 |
42 |
6 |
58 |
52 |
63 |
54 |
10 |
80 |
71 |
86 |
75 |
16 |
107 |
96 |
115 |
100 |
25 |
138 |
119 |
149 |
127 |
35 |
171 |
147 |
185 |
158 |
50 |
209 |
179 |
225 |
192 |
70 |
269 |
229 |
289 |
246 |
95 |
328 |
278 |
352 |
298 |
120 |
382 |
322 |
410 |
346 |
150 |
441 |
371 |
473 |
399 |
185 |
506 |
424 |
542 |
456 |
240 |
599 |
500 |
641 |
538 |
300 |
693 |
576 |
741 |
621 |
400 |
- |
- |
- |
- |
500 |
- |
- |
- |
- |
630 |
- |
- |
- |
- |
Type Designation |
NI2XY, N2XY, N2X2Y, N2XH, NHXH FE 180, NHXHX FE 180, NHXHX |
|
Single Conductor Cables with a space of min. 1 x Diameter (d) to wall |
Installation:
- Direct
- Open Air |
with contact |
with contact
|
with gap d
|
Installation Method2) |
Installation in Open Air |
Installation in Open Air |
F |
G |
Number of Loaded Conductors |
2 |
3 |
3 |
3 |
3 |
Cross-section in mm² |
Current Ratings in Ampere (A) |
1.5 |
- |
- |
- |
- |
- |
2.5 |
- |
- |
- |
- |
- |
4 |
- |
- |
- |
- |
- |
6 |
- |
- |
- |
- |
- |
10 |
- |
- |
- |
- |
- |
16 |
- |
- |
- |
- |
- |
25 |
161 |
141 |
135 |
182 |
161 |
35 |
200 |
176 |
169 |
226 |
201 |
50 |
242 |
216 |
207 |
275 |
246 |
70 |
310 |
279 |
268 |
353 |
318 |
95 |
377 |
342 |
328 |
430 |
389 |
120 |
437 |
400 |
383 |
500 |
454 |
150 |
504 |
464 |
444 |
577 |
527 |
185 |
575 |
533 |
510 |
661 |
605 |
240 |
679 |
634 |
607 |
781 |
719 |
300 |
783 |
736 |
703 |
902 |
833 |
400 |
940 |
868 |
823 |
1085 |
1008 |
500 |
1083 |
998 |
946 |
1253 |
1169 |
630 |
1254 |
1151 |
1088 |
1454 |
1362 |
Conversion factors for deviating ambient temperature, grouping, installation under the ceiling, multi conductor cables and insulated wires - see DIN VDE 0298 part 4.
1) The current ratings are valid for cables with concentric conductor, only for multi conductor versions
2) For further installation methods – see DIN VDE 0298 part 4
|