Operating temperature at conductor 70°C; Ambient temperature 30°C
| Type Designation |
H07V-U, -R, -K
H07V3-U, -R, -K |
NYM, NYMZ, NYMT, NHYRUZY, NYBUY, NYDY, N05VV-U, N05VV-R, NHXMH, NYY, NYCY 1) |
Installation:
- in thermally insulated walls
- in insulating tubes |
Single conductor cables in insulated tubes

|
Multi conductor cables w/ jacket in insulated tubes  |
| Installation Method2) |
Installation in thermally insulated walls |
| A1 |
A2 |
| Number of Loaded Conductors |
2 |
3 |
2 |
3 |
| |
| Cross-section in mm² |
Current Ratings in Ampere (A) |
| 1.5 |
15.53) |
13.5 |
15.53) |
13.0 |
| 2.5 |
19.5 |
18.0 |
18.5 |
17.5 |
| 4 |
26 |
24 |
25 |
23 |
| 6 |
34 |
31 |
32 |
29 |
| 10 |
46 |
42 |
43 |
39 |
| 10 |
- |
- |
- |
- |
| 16 |
61 |
56 |
57 |
52 |
| 25 |
80 |
73 |
75 |
68 |
| 35 |
99 |
89 |
92 |
83 |
| 50 |
119 |
108 |
110 |
99 |
| 70 |
151 |
136 |
139 |
125 |
| 95 |
182 |
164 |
167 |
150 |
| 120 |
210 |
188 |
192 |
172 |
| 150 |
240 |
216 |
219 |
196 |
| 185 |
273 |
245 |
248 |
223 |
| 240 |
320 |
286 |
291 |
261 |
| 300 |
367 |
328 |
334 |
298 |
| Type Designation |
H07V-U, -R, -K
H07V3-U, -R, -K |
NYM, NYMZ, NYMT, NHYRUZY, NYBUY, NYDY, N05VV-U, N05VV-R, NHXMH, NYY, NYCY 1) |
Installation:
- in thermally insulated walls
- in insulating tubes |
Single conductor cables in insulated tubes on a wall
 |
Multi conductor cables w/ jacket in insulated tubes on a wall
 |
| Installation Method2) |
Installation in Insulated Tubes |
| B1 |
B2 |
| Number of Loaded Conductors |
2 |
3 |
2 |
3 |
| |
| Cross-section in mm² |
Current Ratings in Ampere (A) |
| 1.5 |
17.5 |
15.5 |
16.5 |
15 |
| 2.5 |
24 |
21 |
23 |
20 |
| 4 |
32 |
28 |
30 |
27 |
| 6 |
41 |
36 |
38 |
34 |
| 10 |
57 |
50 |
52 |
46 |
| 10 |
- |
- |
- |
47.174) |
| 16 |
76 |
68 |
69 |
62 |
| 25 |
101 |
89 |
90 |
80 |
| 35 |
125 |
110 |
111 |
99 |
| 50 |
151 |
134 |
133 |
118 |
| 70 |
192 |
171 |
168 |
149 |
| 95 |
232 |
207 |
201 |
179 |
| 120 |
269 |
239 |
232 |
206 |
| 150 |
- |
- |
- |
- |
| 185 |
- |
- |
- |
- |
| 240 |
- |
- |
- |
- |
| 300 |
- |
- |
- |
- |
Conversion factors for deviating ambient temperature, grouping, installation under the ceiling, multi conductor cables and insulated wires - see DIN VDE 0298 part 4.
1) The current ratings are valid for cables with concentric conductor, only for multi conductor versions
2) For further installation methods – see DIN VDE 0298 part 4
3) See DIN VDE 0298 part 4
4) Not permitted for the installation on a wooden wall and not for application of the conversion factors, see DIN VDE 0298 part 4
|