Designation Code for Power Cables - according to DIN VDE 0271 / 0276
|
|
|
Identification of Designation
| N |
- |
DIN VDE Standard |
| (N) |
- |
Similar to DIN VDE Standard |
|
|
|
Conductor Material
| A |
- |
Aluminum conductor |
| - |
- |
Copper conductor |
|
|
|
Insulating Materials
| Y |
- |
PVC |
| 2X |
- |
Cross-linked PE (XLPE)
Impregnated paper |
|
|
|
Concentric Conductor (Shielding)
| C |
- |
Concentric Copper Conductor |
| CW |
- |
Concentric Copper Conductor in wave-conal formation |
| CE |
- |
Concentric Copper Conductor over each individual conductor |
| S |
- |
Shielding of Copper Wires |
| SE |
- |
Shielding of Copper Wires over each individual conductor |
| H |
- |
Conductive layers |
| (F) |
- |
Longitudinally water-proof shielding |
|
|
|
Armoring
| B |
- |
Steel tape armoring |
| F |
- |
Armor of galvanized flat steel wires |
| G |
- |
counter helix of galvanized steel tape |
| R |
- |
Armor of galvanized round steel wires |
|
|
|
Jacket Material
| A |
- |
Outer jacket made of fiber material |
| K |
- |
Lead jacket |
| KL |
- |
Aluminum jacket |
| Y |
|
PVC |
| 2Y |
|
PE |
|
|
|
Protective Conductor
| I |
- |
with protective conductor |
| O |
- |
without protective conductor |
|
|
|
| Number of Conductors |
|
|
| Conductor cross-section in mm² |
|
|
Conductor Type
| r ... |
- |
Circular conductor |
| s ... |
- |
Sector conductor |
| o ... |
- |
Oval conductor |
| e ... |
- |
Circular, solid conductor |
| .. m |
- |
Stranded conductor |
| .. h |
- |
Hollow circular conductor |
| /V |
- |
Compact conductor |
|
|
|
Rating Voltage
| 0.6/1 kV |
| 3.6/6 kV |
| 6/10 kV |
| 12/20 kV |
| 18/30 kV |
|