Your One-Stop Solution For Cable & Wire Accessories!

RoHS Compliant Cables & Wires
Technical Information


Contact Us Site Map  
 
Follow us:  LinkedIn Facebook Twitter Hi Tech Controls Blog
Cables & WiresEnclosures (Plastic & Metal)Pneumatic ComponentsLiquid Tight Strain Relief FittingsCircular ConnectorsConduit System (Tubing, Fittings, etc.)Accessories & Adapters, Reducers, Enlargers
 
easyquote
*E-mail
*Name
*Company
*Phone
*State
*Zip Code
*Country
(*) Required Fields
Catalogs / Samples, Full Quote & Contact Information
Quote Request 1-800-677-8942
Catalog & Samples
Contact Information, Phone
dropdownbox
dropdownbox

THE EXCLUSIVE IMPORTER OF Helukabel Cables & Wires
WE PROVIDE CUSTOMERS WITH CABLE MANAGEMENT SOLUTIONS!
-Quantity Discounts! -No Minimum Orders! -Inventory in Excess of $25 Million!
-Blanket Orders! -Quick and Friendly Service! -All Major Credit Cards!

Electrical Characteristics of XLPE-insulated Medium Voltage Power Cables, 6-30 kV

Conductor resistance at 20°C
Cross-section mm² Maximal Value
Copper conductor
Ohm/km
Aluminum conductor
Ohm/km
25 0.727 1.20
35 0.524 0.868
50 0.387 0.641
70 0.268 0.443
95 0.193 0.320
120 0.153 0.253
150 0.124 0.206
185 0.0991 0.164
240 0.0754 0.125
300 0.0601 0.100
400 0.0470 0.0778
500 0.0366 0.0605

Conversion factor for conductor temperatures
Temperature 60°C 65°C 70°C 80°C 90°C
Copper conductor 1.157 1.177 1.196 1.236 1.275
Aluminum conductor 1.161 1.181 1.202 1.242 1.282

Conversion formula
Rδ = R20 x 234.5 + δ   for copper conductor
254.5

Rδ = R20 x 228 + δ   for aluminum conductor
248

δ = Conductor temperature
= Conductor resistance in Ohm/km
R20 = Conductor resistance at 20°C in Ohm/km

to top up arrow
Effective resistance at 50 Hz (alternating current resistance)
Copper or Aluminum Conductor
Conductor Material Copper Conductor Aluminum Conductor
Arrangement Copper Conductor - 6/10 kV Copper Conductor - 6/10 kV Copper Conductor - 12/20 kV Copper Conductor - 12/20 kV Copper Conductor - 18/30 kV Copper Conductor - 18/30 kV Aluminum Conductor - 6/10 kV Aluminum Conductor - 6/10 kV Aluminum Conductor - 12/20 kV Aluminum Conductor - 12/20 kV Aluminum Conductor - 18/30 kV Aluminum Conductor - 18/30 kV
U0/U 6/10 kV 12/20 kV 18/30 kV 6/10 kV 12/20 kV 18/30 kV
Cross-section mm² Effective Resistance
35 0.671 0.673 0.671 0.672 - - 1.12 1.12 1.12 1.12 - -
50 0.497 0.498 0.496 0.498 0.496 0.497 0.825 0.826 0.825 0.826 0.824 0.826
70 0.345 0.346 0.345 0.346 0.344 0.346 0.571 0.572 0.571 0.572 0.571 0.572
95 0.249 0.251 0.249 0.250 0.249 0.250 0.413 0.415 0.413 0.414 0.413 0.414
120 0.198 0.200 0.198 0.200 0.198 0.199 0.327 0.329 0.327 0.329 0.327 0.328
150 0.163 0.165 0.163 0.165 0.162 0.164 0.269 0.271 0.268 0.270 0.268 0.270
185 0.132 0.134 0.131 0.133 0.131 0.133 0.215 0.217 0.215 0.217 0.214 0.216
240 0.102 0.104 0.101 0.103 0.101 0.103 0.165 0.167 0.165 0.167 0.164 0.166
300 0.082 0.085 0.082 0.084 0.082 0.084 0.133 0.135 0.133 0.135 0.133 0.135
400 0.068 0.071 0.067 0.070 0.067 0.069 0.106 0.109 0.106 0.109 0.106 0.108
500 0.055 0.058 0.055 0.058 0.054 0.057 0.085 0.088 0.084 0.087 0.084 0.087

Inductive resistance at 50 Hz
Conductor Material Copper Conductor
Arrangement Conductor - 6/10 kV Conductor - 6/10 kV Conductor - 12/20 kV Conductor - 12/20 kV Conductor - 18/30 kV Conductor - 18/30 kV
U0/U 6/10 kV 12/20 kV 18/30 kV
Cross-section mm² Inductive Resistance
35 0.144 0.158 0.153 0.168 - -
50 0.136 0.150 0.145 0.159 0.154 0.169
70 0.129 0.143 0.138 0.152 0.147 0.161
95 0.123 0.137 0.131 0.145 0.139 0.154
120 0.118 0.132 0.126 0.140 0.134 0.148
150 0.114 0.128 0.121 0.135 0.129 0.143
185 0.110 0.124 0.117 0.131 0.125 0.139
240 0.105 0.120 0.112 0.126 0.120 0.134
300 0.102 0.116 0.108 0.123 0.115 0.130
400 0.097 0.111 0.103 0.117 0.110 0.124
500 0.094 0.108 0.100 0.114 0.106 0.120

Mutual capacitance
Nominal Voltage 6/10 kV 12/20 kV 18/30 kV
Cross-section mm² Mutual Capacitance in μF/km
35 0.22 0.16 -
50 0.25 0.18 0.14
70 0.28 0.20 0.15
95 0.31 0.22

0.17

120 0.34 0.23 0.18
150 0.37 0.25 0.19
185 0.40 0.27 0.20
240 0.44 0.30 0.22
300 0.48 0.32 0.24
400 0.55 0.36 0.27
500 0.60 0.40 0.29
to top up arrow
Inductance
Nominal Voltage 6/10 kV 12/20 kV 18/30 kV
  Conductor - 6/10 kV Conductor - 6/10 kV Conductor - 12/20 kV Conductor - 12/20 kV Conductor - 18/30 kV Conductor - 18/30 kV
Cross-section mm² Inductance in mH/km
35 0.45 0.76 0.48 0.76 - -
50 0.42 0.73 0.45 0.74 0.48 0.75
70 0.39 0.70 0.43 0.70 0.45 0.71
95 0.38 0.67 0.41 0.68 0.43 0.68
120 0.36 0.65 0.39 0.65 0.42 0.66
150 0.35 0.63 0.38 0.63 0.41 0.64
185 0.34 0.61 0.36 0.62 0.39 0.63
240 0.32 0.59 0.35 0.59 0.37 0.60
300 0.31 0.57 0.33 0.58 0.36 0.59
400 0.30 0.55 0.33 0.55 0.34 0.56
500 0.29 0.53 0.31 0.53 0.33 0.54

Short circuit current carrying capacity up to 30 kV
Conductor temperature: 90°C
Short circuit temperature: 250°C

Cable with Copper conductors
Cross-section mm² Short circuit time in s (seconds)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.5 2.0 3.0 4.0 5.0
Permissible short circuit in kA
25 11.3 8.0 6.5 5.7 5.1 4.6 4.3 4.0 3.8 3.6 2.9 2.5 2.1 11.8 1.6
35 15.8 11.2 9.1 7.9 7.1 6.5 6.0 5.6 5.3 5.0 4.1 3.5 2.9 2.5 2.2
50 22.6 16.0 13.1 11.3 10.1 9.2 8.5 8.0 7.5 7.2 5.8 5.1 4.1 3.6 3.2
70 31.7 22.4 18.3 15.8 14.2 12.9 12.0 11.2 10.6 10.0 8.2 7.1 5.8 5.0 4.5
95 43.0 30.4 24.8 21.5 19.2 17.5 16.2 15.2 14.3 13.6 11.1 9.6 7.8 6.8 6.1
120 54.3 38.4 31.3 27.1 24.3 22.2 20.5 19.2 18.1 17.2 14.0 12.1 9.9 8.6 7.7
150 67.8 48.0 39.2 33.9 30.3 27.7 25.6 24.0 22.6 21.5 17.5 15.2 12.4 10.7 9.6
185 83.7 59.2 48.3 41.8 37.4 34.2 31.6 29.6 27.9 26.5 21.6 18.7 15.3 13.2 11.8
240 108.5 76.7 62.7 54.3 48.5 44.3 41.0 38.4 36.2 34.3 28.0 24.3 19.8 17.2 15.3
300 135.7 95.9 78.3 67.8 60.7 55.4 51.3 48.0 45.2 42.9 35.0 30.3 24.8 21.5 19.2
400 180.9 127.9 104.4 90.4 80.9 73.8 68.4 64.0 60.3 57.2 46.7 40.4 33.0 28.6 25.6
500 226.1 159.9 130.5 113.1 101.1 92.3 85.5 79.9 75.4 71.5 58.7 50.6 41.3 35.8 32.0

Cables with Aluminum conductors
Cross-section mm² Short circuit time in s (seconds)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.5 2.0 3.0 4.0 5.0
Permissible short circuit in kA
25 7.4 5.3 4.3 3.7 3.3 3.0 2.8 2.6 2.5 2.4 1.9 1.7 1.4 1.2 1.1
35 10.4 7.4 6.0 5.2 4.7 4.2 3.9 3.7 3.5 3.3 2.7 2.3 1.9 1.6 1.5
50 14.9 10.5 8.6 7.4 6.6 6.1 5.6 5.3 5.0 4.7 3.8 3.3 2.7 2.4 2.1
70 20.8 14.7 12.0 10.4 9.3 8.5 7.9 7.4 6.9 6.6 5.4 4.7 3.8 3.3 2.9
95 28.2 20.0 16.3 14.1 12.6 11.5 10.7 10.0 9.4 8.9 7.3 6.3 5.2 4.5 4.0
120 35.7 25.2 20.6 17.8 16.0 14.6 13.5 12.6 11.9 11.3 9.2 8.0 6.5 5.6 5.0
150 44.6 31.5 25.7 22.3 19.9 18.2 16.9 15.8 14.9 14.1 11.5 10.0 8.1 7.1 6.3
185 55.0 38.9 31.7 27.5 24.6 22.5 20.8 19.4 18.3 17.4 14.2 12.3 10.0 8.7 7.8
240 71.3 50.4 41.2 35.7 31.9 29.1 27.0 25.2 23.8 22.6 18.4 16.0 13.0 11.3 10.1
300 89.2 63.1 51.5 44.6 39.9 36.4 33.7 31.5 29.7 28.2 23.0 19.9 16.3 14.1 12.6
400 118.9 87.1 68.6 59.5 53.2 48.5 44.9 42.0 39.6 37.6 30.7 26.6 21.7 18.8 16.8
500 146.8 105.1 85.8 74.3 66.5 60.7 56.2 52.5 49.5 47.0 38.4 33.2 27.1 23.5 21.0
to top up arrow
Short circuit to ground
Nominal Voltage 6/10 kV 12/20 kV 18/30 kV
Cross-section mm² A/km
35 1.2 1.7 -
50 1.4 1.9 2.3
70 1.5 2.1 2.5
95 1.7 2.4 2.7
120 1.9 2.6 2.9
150 2.0 2.7 3.1
185 2.2 3.0 3.3
240 2.4 3.3 3.7
300 2.6 3.5 4.0
400 3.0 4.0 4.4
500 3.3 4.3 4.8

Short circuit to current carrying capacity of copper shielding
Short circuit temperature: 250°C
Short circuit time in seconds up to 16 mm² 25 mm² 35 mm²
Load of short circuit current in kA
0.1 9.7 15.1 21.2
0.2 6.9 10.7 15.1
0.3 5.7 8.9 12.5
0.4 5.0 7.7 10.9
0.5 4.5 7.0 9.8
0.6 4.2 6.4 9.0
0.7 3.9 6.0 8.4
0.8 3.5 5.6 7.9
0.9 3.4 5.3 7.5
1.0 3.3 5.1 7.2
1.5 2.7 4.2 5.9
2.0 2.3 3.6 5.1
3.0 1.9 2.9 4.2
4.0 1.7 2.6 3.6
5.0 1.5 2.3 3.2
to top up arrow
quote
Items For Quote

   
quote
box

Sealcon is the Exclusive Importer of HUMMEL products. We offer over 6,000 different Types and Sizes of RoHS Compliant Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands, Circular Connectors, Conduit System, Industrial Enclosures and Other Related Cable Management Products which are rated the best in the industry.
Liquid Tight Strain Relief, Cord Grips, Cable Gland FittingsLiquid Tight Strain Relief Fittings, Cord Grips, Cable Glands
Threads: PG, NPT, Metric, BSPP Threads
Materials: Nylon, Nickel Plated Brass, PVDF (for chemicals and extreme temperatures) & Stainless Steel, NEMA 4x and 6 (IP68, IP 69K).
Approvals: RoHS, Deca BDE, UR, UL, CE, CSA, VDE, German Lloyd, etc.
UL f1 (UL 746C) - Suitable for outdoor use with respect to exposure to ultraviolet light, water exposure and immersion in accordance with UL 746C
Circular ConnectorsCircular Connectors (M16, M23, RJ45, M27 and M40)
Sizes: M16 Signal, M23 Signal & Power, M27 Signal, M40 Power, M12/16 Twintus
Types: Twintus, RJ45 Industrial Ethernet, PoE Fast Ethernet, Push-Pull, Stainless Steel, Over Molded Cordsets, Standard/EMI Ready
Configurations: Signal (3-28 pole) & Power (6 & 8 pole)
Materials: Nickel Plated Brass, Stainless Steel and Aluminum
Approvals: RoHS, Deca BDE, UR, UL, CSA, TÜV, etc.
Hummel EnclosuresIndustrial Enclosures (Plastic & Metal)
Materials: Polycarbonate, ABS (Acryl-Butadiene-Styrene), Aluminum, Steel/Stainless Steel and Polyester.
Types: Gray or Transparent Lids, available with Hinges and Latches, Plain Walls or Knockouts.
Approvals: RoHS, Deca BDE, UL, CSA, TUV and CE. Modular, Expandable, UV and Impact Resistant, NEMA 4, 4x (IP 66/67). Solar Plus for Photovoltaic applications.
Our Enclosures can be equipped with Strain Relief Fittings, Circular Connectors or Conduit Fittings. Other customization options like cutting & drilling are also available.
Conduit SystemConduit System
High Pull-Out Resistance, Robust Performance, Long Life Expectancy, Fastest/ Easy installation, No Tools required!
Fittings:
Push-In, Turn-to-Seal, Snapclic DUO (Nylon or Nickel Plated Brass), Double-Seal, Flange/Bulkhead
Conduit:
Standard and Super Flex Corrugated Conduit
Accessories: Snap-In Mounting Brackets. NEMA 4 (IP 54/65)
Approvals: RoHS, Deca BDE, UR, German Lloyd, CE, etc.
Hazardous Location / Explosive Proof Cord Grips, Cable GlandsHazardous Location / Explosive Proof Cord Grips, Cable Glands
These fittings are labeled and approved to withstand the required needs of a combustible environment.
Materials: Nylon, Nickel Plated Brass, PVDF (chemical resistant & extreme temperatures), Stainless Steel.
Threads: NPT, Metric & PG. NEMA 4x (IP 67) and 6 (IP 68/69K)
Approvals:
RoHS, Deca BDE, UL, CSA, VDE, CE, EEx e, ATEX, German Lloyd, IECEx,
Ex-d/Ex-e, Ex-i
EXIOS - High-end Cable Glands for armored cables in hazardous areas including the latest IECEx and ATEX certifications, for use in Ex-e, Ex-d and Ex-tD areas
Adapters, Enlargers, ReducersThread Adapters, Enlargers, Reducers
Convert, Increase or Decrease your thread size with our newest product line of Adapters, Enlargers and Reducers.
Threads: NPT, Metric and PG.
Materials: Black or Gray Nylon, Nickel Plated Brass, Aluminum, Stainless Steel.
Approvals: RoHS, Deca BDE, CE, EEe x, ATEX, etc.
Hazardous / Explosive proof versions available.
Cable AccessoriesCable Accessories
Locking Nuts:Black & Gray Nylon, Nickel Plated Brass, Zinc Plated Steel, EMI (w/ Cutting Edges)
O-Rings: Buna-N, Viton®, Silicone
Seal Rings: Polyethylene / Fiber-reinforced Plastic
Hole Plugs: Dome, Hex, Nylon, Nickel Plated Brass
Inserts: Standard, Reduced, Multi-Hole, Romex®
Other Accessories: Ratchet & Socket Wrenches, Cable Clamps, etc.
14853 E. Hinsdale Ave.
Centennial, CO 80112-4240 USA
Toll Free: 800-677-8942 / 303-680-5159 FAX: 303-680-5344
Valid XHTML 1.0 Transitional
To Top of Page Top of Page

Copyright © 2012 Hi-Tech Controls Inc. All Rights Reserved
|Cables: Domestic & International|Enclosures (Plastic & Metal)|Liquid Tight Strain Relief Fittings & Accessories|
|Circular Connectors|Conduit System|Camozzi Pneumatics|Cable Index|Enclosure Index|Search|
|Media|Site Map|Company Overview|Contact|Privacy Policy|Copyright Notice|