Temperature Range Flexing +5°C to
+70°C
Fixed Installation -40°C
to +70°C
Nominal Voltage 0.14 mm² = 350
V
>0.14 mm² = 500
V
Test Voltage 0.14 mm² = 800
V
>0.14 mm² = 1200
V
Insulation Resistance Min. 2 GOhm x km
Capacitance Conductor/conductor <70
nF/km
Minimum Bending Radius Approx. 7.5x cableØ
Radiation Resistance Up to 100x106 cJ/kg (up
to 100 Mrad)
Approvals
Cable
Construction
Bare copper, fine wire conductors
to DIN VDE 0812, conductor make-up
for 0.34 mm² - 7x0.25 mm
PE-insulation, compound type 2YJ1
to DIN VDE 0207 part 2
Conductors color coded to DIN 47100
Conductors twisted in layers with optimal
lay-length
Halogen-free outer jacket, to DIN
VDE 0207 part 24, compound type HM2
Jacket color: Gray, RAL 7005
Application
DATAFLAMM halogen-free
data cable
are used as connecting cable for
signal, measuring, control, call-announcing
and two-way intercom speaking systems,
clock installations, electronic
weighting equipment and electrical
apparatus for office requirements.
The cables are suitable for installation
in dry, damp and wet environments
as well as in concrete. PE-insulated
conductors, compared with the conventional
PVC-insulated conductors, assure a remarkable
and more favorable capacitance
value. These cables are generally
installed in telecommunication
apparatus and data transmission
systems in public buildings, laboratories,
trading centers where the freedom
from halogen in case of fire and
flame propagation must be avoided.
The halogen-free thermoplastic
jacket produces neither corrosive
nor toxic gases.
=
The product
is conformed
with
the EC
Low-Voltage
Directive
73/23/EEC
and 93/68/EEC.
Properties
Halogen-free according to
DIN VDE 0482 part 267 / EN 50267-2-1 /
IEC 60754-1 (equivalent DIN
VDE 0472 part 815)
Corrosiveness of combustion
gases according to VDE
0482 part 267 / DIN EN 50267-2-2 /
IEC 60754-2 (equivalent DIN
VDE 0472 part 813)
Halogen-free jacket compound,
self-extinguishing and flame
retardant according to DIN
VDE 0482 part 265-2-1 / EN 50265-2-1 /
IEC 60332-1 (equivalent DIN
VDE 0472 part 804 test method
B)
Note
AWG sizes are approximate equivalent
values. the actual cross-section is
in mm2
is the Exclusive Importer of HUMMEL products. We offer over 6,000 different Types and Sizes of RoHS Compliant Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands, Circular Connectors, Conduit System, Industrial Enclosures and Other Related Cable Management Products which are rated the best in the industry.
7374 S. Eagle Street
Centennial, CO 80112-4221 USA
Toll Free: 800-456-9012 / 303-699-1135 FAX: 303-680-5344